RULE §115.177Fugitive Emission Component Requirements

paragraph (7) of this subsection.

  (9) Monitored screening concentrations must be recorded for each component in gaseous or light liquid service. Notations such as "pegged," "off scale," "leaking," "not leaking," or "below leak definition" may not be substituted for hydrocarbon gas analyzer results. For readings that are higher than the upper end of the scale (i.e., pegged) even when using the highest scale setting or a dilution probe, a default pegged value of 100,000 ppmv must be recorded. This requirement does not apply to monitoring using an optical gas imaging instrument, which makes emissions visible that may otherwise be invisible to the naked eye, in accordance with §115.358 of this title.

  (10) The owner or operator shall check all new connectors for leaks within 30 days of being placed in VOC service by monitoring with a hydrocarbon gas analyzer for components in light-liquid and gas service and by using visual, audio, and/or olfactory means for components in heavy-liquid service. Components that are unsafe-to-monitor or inspect are exempt from this requirement if they are monitored or inspected as soon as possible during times that are safe to monitor.

  (11) For any fugitive emission component for which the owner or operator elects to use the alternative work practice in §115.358 of this title, the following provisions apply.

    (A) At a natural gas processing plant, the frequency for monitoring components listed in this section must be the frequency determined according to §115.358 of this title. At a well site or gathering and boosting station, the frequency for monitoring components using optical gas imaging is the frequency in paragraph (3) of this subsection.

    (B) The alternative monitoring schedules allowed under paragraph (7) of this subsection are not allowed.

    (C) At a well site or gathering and boosting station, the requirements in §115.358 of this title, except for the requirements in §115.358(e) and (f) of this title, apply in addition to the appropriate requirements in this section. At a natural gas processing plant, the requirements in §115.358 of this title apply in addition to the applicable requirements in this section.

    (D) The owner or operator may still classify a component as unsafe-to-monitor as allowed under subsection (c) of this section if the component cannot safely be monitored using either a hydrocarbon gas analyzer or the alternative work practice. The owner or operator may use either EPA Method 21 in 40 CFR Part 60, Appendix A-7 or the alternative work practice at the monitoring frequency specified in paragraph (3) of this subsection. Any component classified as unsafe-to-monitor under the alternative work practice must be identified as such in the list required in §115.180(7) of this title.

    (E) If the executive director determines that there is an excessive number of leaks in any given process area for which the alternative work practice in §115.358 of this title is used, the executive director may require an increase in the frequency of monitoring under the alternative work practice in that process area.

(c) An owner or operator is not required to comply with monitoring frequencies in subsection (b) of this section for any fugitive emission component designated as unsafe-to-monitor or difficult-to-monitor.

  (1) Any component, except closed vent systems, designated difficult-to-monitor must be monitored at least once per calendar year. Difficult-to-monitor closed vent system components must be monitored at least once every five years.

  (2) Any component designated unsafe-to-monitor must be monitored as frequently as practicable during a time when it is safe-to-monitor, not to exceed the monitoring frequency in subsection (b) of this section.

  (3) The number of components designated as difficult-to-monitor may not exceed 3% of total affected components in the same classification (e.g., pumps, valves, flanges, connectors etc.) at the site.

  (4) The owner or operator shall inspect all flanges weekly by audio, visual, and olfactory means, excluding flanges that are monitored at least once each calendar year using EPA Method 21 in 40 CFR Part 60, Appendix A-7 and flanges that are difficult-to-monitor and unsafe-to-monitor. Flanges that are difficult-to-monitor and unsafe-to-monitor must be identified in a list made available upon request. If a difficult-to-monitor or an unsafe-to-monitor flange is not considered safe to inspect within the required weekly time frame, then it must be inspected as soon as possible during a time that it is safe to inspect.

  (5) Relief valves that are designated as unsafe-to-monitor must be monitored as soon as possible during times that are safe to monitor after any release event. Relief valves that are designated as difficult-to-monitor must be monitored within 15 days after a release.


Source Note: The provisions of this §115.177 adopted to be effective July 21, 2021, 46 TexReg 4313