RULE §117.340Continuous Demonstration of Compliance

(a) Totalizing fuel flow meters. The owner or operator of units listed in this subsection shall install, calibrate, maintain, and operate a totalizing fuel flow meter, with an accuracy of ± 5%, to individually and continuously measure the gas and liquid fuel usage. A computer that collects, sums, and stores electronic data from continuous fuel flow meters is an acceptable totalizer. The owner or operator of units with totalizing fuel flow meters installed prior to March 31, 2005, that do not meet the accuracy requirements of this subsection shall either recertify or replace existing meters to meet the ± 5% accuracy required as soon as practicable but no later than March 31, 2007. For the purpose of compliance with this subsection for units having pilot fuel supplied by a separate fuel system or from an unmonitored portion of the same fuel system, the fuel flow to pilots may be calculated using the manufacturer's design flow rates rather than measured with a fuel flow meter. The calculated pilot fuel flow rate must be added to the monitored fuel flow when fuel flow is totaled.

  (1) The units are the following:

    (A) for units that are subject to §117.305 of this title (relating to Emission Specifications for Reasonably Available Control Technology (RACT)), for stationary gas turbines that are exempt under §117.303(b)(7) of this title (relating to Exemptions):

      (i) if individually rated more than 40 million British thermal units per hour (MMBtu/hr):

        (I) boilers;

        (II) process heaters;

        (III) boilers and industrial furnaces that were regulated as existing facilities by 40 Code of Federal Regulations (CFR) Part 266, Subpart H, as was in effect on June 9, 1993; and

        (IV) gas turbine supplemental-fired waste heat recovery units;

      (ii) stationary reciprocating internal combustion engines not exempt by §117.303(a)(6), (a)(8), (b)(9), or (b)(10) of this title;

      (iii) stationary gas turbines with a megawatt (MW) rating greater than or equal to 1.0 MW operated more than 850 hours per year; and

      (iv) fluid catalytic cracking unit boilers using supplemental fuel; and

    (B) for units subject to §117.310 of this title (relating to Emission Specifications for Attainment Demonstration):

      (i) boilers (excluding wood-fired boilers that must comply by maintaining records of fuel usage as required in §117.345(f) of this title (relating to Notification, Recordkeeping, and Reporting Requirements) or monitoring in accordance with paragraph (2)(A) of this subsection);

      (ii) process heaters;

      (iii) boilers and industrial furnaces that were regulated as existing facilities by 40 CFR Part 266, Subpart H, as was in effect on June 9, 1993;

      (iv) duct burners used in turbine exhaust ducts;

      (v) stationary, reciprocating internal combustion engines;

      (vi) stationary gas turbines;

      (vii) fluid catalytic cracking unit boilers and furnaces using supplemental fuel;

      (viii) lime kilns;

      (ix) lightweight aggregate kilns;

      (x) heat treating furnaces;

      (xi) reheat furnaces;

      (xii) magnesium chloride fluidized bed dryers; and

      (xiii) incinerators (excluding vapor streams resulting from vessel cleaning routed to an incinerator, provided that fuel usage is quantified using good engineering practices, including calculation methods in general use and accepted in new source review permitting in Texas. All other fuel and vapor streams must be monitored in accordance with this subsection.)

  (2) The following are alternatives to the fuel flow monitoring requirements of paragraph (1) of this subsection.

    (A) Units operating with a nitrogen oxides (NOX ) and diluent continuous emissions monitoring system (CEMS) under subsection (f) of this section may monitor stack exhaust flow using the flow monitoring specifications of 40 CFR Part 60, Appendix B, Performance Specification 6 or 40 CFR Part 75, Appendix A.

    (B) Units that vent to a common stack with a NOX and diluent CEMS under subsection (f) of this section may use a single totalizing fuel flow meter.

    (C) Diesel engines operating with run time meters may meet the fuel flow monitoring requirements of this subsection through monthly fuel use records maintained for each engine.

    (D) Stationary reciprocating internal combustion engines and stationary gas turbines equipped with a continuous monitoring system that continuously monitors horsepower and hours of operation are not required to install totalizing fuel flow meters. The continuous monitoring system must be installed, calibrated, maintained, and operated according to manufacturers' recommended procedures.

(b) Oxygen (O2) monitors.

  (1) The owner or operator shall install, calibrate, maintain, and operate an O2 monitor to measure exhaust O2 concentration on the following units operated with an annual heat input greater than 2.2(1011 ) British thermal units per year (Btu/yr):

    (A) boilers with a rated heat input greater than or equal to 100 MMBtu/hr; and

    (B) process heaters with a rated heat input greater than or equal to 100 MMBtu/hr, except as provided in subsection (g) of this section.

  (2) The following are not subject to this subsection:

    (A) units listed in §117.303(b)(3) - (5) and (8) - (10) of this title;

    (B) process heaters operating with a carbon dioxide CEMS for diluent monitoring under subsection (g) of this section; and

    (C) wood-fired boilers.

  (3) The O2 monitors required by this subsection are for process monitoring (predictive monitoring inputs, boiler trim, or process control) and are only required to meet the location specifications and quality assurance procedures referenced in subsection (f) of this section if O2 is the monitored diluent under that subsection. However, if new O2 monitors are required as a result of this subsection, the criteria in subsection (f) of this section should be considered the appropriate guidance for the location and calibration of the monitors.

(c) NOX monitors.

  (1) The owner or operator of units listed in this paragraph shall install, calibrate, maintain, and operate a CEMS or predictive emissions monitoring system (PEMS) to monitor exhaust NOX . The units are:

    (A) boilers with a rated heat input greater than or equal to 250 MMBtu/hr and an annual heat input greater than 2.2(1011 ) Btu/yr;

    (B) process heaters with a rated heat input greater than or equal to 200 MMBtu/hr and an annual heat input greater than 2.2(1011 ) Btu/yr;

    (C) stationary gas turbines with an MW rating greater than or equal to 30 MW operated more than 850 hours per year;

    (D) units that use a chemical reagent for reduction of NOX ;

    (E) units that the owner or operator elects to comply with the NOX emission specifications of §117.305 of this title using a pound per MMBtu (lb/MMBtu) limit on a 30-day rolling average;

    (F) lime kilns and lightweight aggregate kilns;

    (G) units with a rated heat input greater than or equal to 100 MMBtu/hr that are subject to §117.310(a) of this title; and

    (H) fluid catalytic cracking units (including carbon monoxide (CO) boilers, CO furnaces, and catalyst regenerator vents). In addition, the owner or operator shall monitor the stack exhaust flow rate with a flow meter using the flow monitoring specifications of 40 CFR Part 60, Appendix B, Performance Specification 6 or 40 CFR Part 75, Appendix A.

  (2) The following are not required to install CEMS or PEMS under this subsection:

    (A) for purposes of §117.305 of this title, units listed §117.303(b)(3) - (5) and (8) - (10) of this title; and

    (B) units subject to the NOX CEMS requirements of 40 CFR Part 75.

  (3) The owner or operator shall use one of the following methods to provide substitute emissions compliance data during periods when the NOX monitor is off-line:

    (A) if the NOX monitor is a CEMS:

      (i) subject to 40 CFR Part 75, use the missing data procedures specified in 40 CFR Part 75, Subpart D (Missing Data Substitution Procedures); or

      (ii) subject to 40 CFR Part 75, Appendix E, use the missing data procedures specified in 40 CFR Part 75, Appendix E, §2.5 (Missing Data Procedures);

    (B) use 40 CFR Part 75, Appendix E monitoring in accordance with §117.1240(e) of this title (relating to Continuous Demonstration of Compliance);

    (C) if the NOX monitor is a PEMS:

Cont'd...