(a) Fire alarm and smoke detection system. A new large
Type B assisted living facility must provide a fire alarm system meeting
the requirements of 18.3.4, Detection, Alarm, and Communications Systems,
in NFPA 101, Chapter 18, New Health Care Occupancies, as modified
by this section.
(1) General. A new large Type B assisted living facility
must ensure the operation of any alarm initiating device automatically
activates the manual fire alarm system evacuation alarm for the entire
building.
(2) Smoke detectors.
(A) A new large Type B assisted living facility must
install smoke detectors meeting the requirements of 18.3.4.5.1, Corridors,
in NFPA 101, Chapter 18, New Health Care Occupancies.
(B) A new large Type B assisted living facility comprised
of buildings containing living units with independent cooking equipment
within the living unit, must additionally have:
(i) a smoke detector installed in all resident bedrooms,
corridors, hallways, living rooms, dining rooms, offices, kitchens
and laundries within the living unit, that sounds an alarm only within
the living unit; and
(ii) a heat detector installed in the kitchen within
the living unit that activates the general alarm.
(3) Alarm control panel.
(A) A new large Type B assisted living facility must
provide a fire alarm control unit, or a fire alarm annunciator providing
annunciation of all fire alarm, supervisory, and trouble signals by
audible and visible indicators, in a location visible to staff at
or near the staff area that is attended 24 hours a day.
(B) A new large Type B assisted living facility is
not required to ensure a fire alarm control unit or fire alarm annunciator
is visible to staff if the fire alarm is monitored by devices carried
by all staff.
(C) A new large Type B assisted living facility must
ensure a fire alarm panel indicates each floor and smoke compartment,
as applicable, as a separate zone. Each zone must provide an alarm
and trouble indication. When all alarm initiating devices are addressable
and the status of each device is identified on the fire alarm panel,
zone indication is not required.
(4) Fire alarm power source.
(A) A new large Type B assisted living facility must
ensure a fire alarm system is powered by a permanently-wired, dedicated
branch circuit that is powered from a commercial power source in accordance
with NFPA 70.
(B) A new large Type B assisted living facility must
provide a secondary, emergency power source meeting the requirements
of NFPA 72.
(5) Emergency forces notification. A new large Type
B assisted living facility must ensure a fire alarm system automatically
notifies emergency forces according to the requirements of 18.3.4.3.2,
Emergency Forces Notification, in NFPA 101, Chapter 18, New Health
Care Occupancies
(b) Fire sprinkler system. A new large Type B assisted
living facility must provide a fire sprinkler system meeting the requirements
of NFPA 13 in accordance with 18.3.5, in NFPA 101, Chapter 18, New
Health Care Occupancies.
(c) Portable Fire Extinguishers. A new large Type B
assisted living facility must provide and maintain portable fire extinguishers
according to the requirements of NFPA 10.
(1) A new large Type B assisted living facility must
ensure all requirements of NFPA 10 are followed for all extinguisher
types, including requirements for location, spacing, mounting heights,
monthly inspections by staff, yearly inspections by a licensed agent,
any necessary servicing, and hydrostatic testing as recommended by
the manufacturer.
(2) A new large Type B assisted living facility must
ensure portable fire extinguishers are located in resident corridors
so the travel distance from any point in the facility to an extinguisher
is no more than 75 feet.
(3) A new large Type B assisted living facility must
ensure the actual size of any portable fire extinguisher meets the
requirements of NFPA 10 for maximum floor area per unit covered, but
an extinguisher must be no smaller than the following.
(A) A water-type portable fire extinguisher must have
a rating of at least 1-A according to NFPA 10.
(B) All other portable fire extinguishers must have
a rating of at least 2-A:10-B:C according to NFPA 10.
(C) A facility must provide at least one approved 20-B:C
portable fire extinguisher in each laundry, kitchen, and walk-in mechanical
room.
(4) A new large Type B assisted living facility must
ensure portable fire extinguishers are installed on hangers or brackets
supplied with the extinguisher or mounted in an approved cabinet.
(5) A new large Type B assisted living facility must
ensure a portable fire extinguisher is protected from impact or dislodgement.
(6) A new large Type B assisted living facility must
ensure a portable fire extinguisher is installed at an appropriate
height.
(A) A portable fire extinguisher having a gross weight
of up to 40 pounds must be installed so the top of the extinguisher
is not more than five feet above the floor.
(B) A portable fire extinguisher having a gross weight
greater than 40 pounds must be installed so the top of the extinguisher
is not more than three and a half feet above the floor.
(C) A portable fire extinguisher must be installed
so the clearance between the bottom of the extinguisher and the floor
is at least four inches.
(7) A portable extinguisher provided in a hazardous
room must be located as close as possible to the exit access door
leading from the room and on the latch or knob side of the door.
|