(a) The facility must be served by a paid or volunteer
fire department. The fire department must provide written assurance
to the licensing agency that the fire department can respond to an
emergency at the facility within an appropriately prompt time for
the travel conditions.
(b) The facility must be served by an adequate water
supply that is satisfactory and accessible for fire department use
as determined by the fire department serving the facility and by HHSC.
(c) There must be at least one approved, readily accessible
fire hydrant located within 300 feet of the building. The hydrant
must be on a minimum six-inch service line, or else there must be
an approved equivalent, such as a storage tank. The hydrant, its location,
and service line, or equivalent must be approved by the local fire
department and HHSC.
(d) The building must have suitable fire lanes for
access as required by local fire authorities and HHSC.
|
Source Note: The provisions of this §554.311 adopted to be effective July 1, 1996, 21 TexReg 4408; amended to be effective August 1, 2000, 25 TexReg 6779; transferred effective January 15, 2021, as published in the Texas Register December 11, 2020, 45 TexReg 8871; amended to be effective January 2, 2022, 46 TexReg 9037 |