RULE §263.50Emergency Electrical Power

(a) New facilities, new additions, and major renovations to existing facilities shall be equipped with an emergency back-up electrical generator designed to operate both manually and automatically upon interruption of the primary electrical power source. The system shall be capable of operating uninterrupted for a minimum period of one and one half hours without refueling. Back-up electrical power shall be provided for necessary equipment and life safety systems including, but not limited to:

  (1) emergency illumination systems;

  (2) exit lights;

  (3) smoke management systems;

  (4) fire detection and alarm systems;

  (5) audible communication systems;

  (6) security/control systems;

  (7) normal ventilation systems required for smoke detection.

(b) Existing facilities shall provide emergency illumination and this may be accomplished by utilizing a battery back-up system capable of continuous operation for one and one-half hours.


Source Note: The provisions of this §263.50 adopted to be effective December 19, 1994, 19 TexReg 9526.