RULE §553.104Safety Operations

(a) Local fire marshal inspection.

  (1) An assisted living facility must obtain an inspection at least once every 12 months, by the local fire marshal, or the Texas State Fire Marshal's Office in locations where there is no local fire marshal, and must correct any items cited by the local fire marshal, or the Texas State Fire Marshal's Office, to the satisfaction of those authorities.

  (2) An assisted living facility must maintain documentation at the facility reflecting the outcome of the most recent annual inspection.

(b) Emergency evacuation floor plan. An assisted living facility, other than a one-story small Type A or a one-story small Type B assisted living facility, must post an emergency evacuation floor plan in a location visible to residents.

(c) Fire safety plan. An assisted living facility must establish a fire safety plan for the protection of all persons in the facility in the event of fire.

  (1) An assisted living facility must ensure the fire safety plan is in effect at all times.

  (2) An assisted living facility must make written copies of the fire safety plan are available to all supervisory personnel.

  (3) An assisted living facility must ensure the fire safety plan addresses:

    (A) evacuation to an area of refuge;

    (B) evacuation from the building when necessary; and

    (C) special staff actions, including fire protection procedures necessary to ensure the safety of any resident.

  (4) If the facility is a large Type B assisted living facility:

    (A) An existing large Type B assisted living facility must ensure the fire safety plan includes the provisions described in 19.7.2, Procedure in Case of Fire, in NFPA 101, Chapter 19, Existing Health Care Occupancies.

    (B) A new large Type B assisted living facility must ensure the fire safety plan includes the provisions described in 18.7.2, Procedure in Case of Fire, in NFPA 101, Chapter 18, New Health Care Occupancies.

  (5) An assisted living facility must ensure the fire safety plan is reviewed at least annually and revised, as needed, to address the changing needs of residents.

  (6) An assisted living facility must instruct and inform all employees of their duties and responsibilities under the fire safety plan at least annually, and when the fire safety plan is revised.

  (7) An assisted living facility must keep a copy of the fire safety plan readily available at all times within the facility.

  (8) An assisted living facility must ensure the fire safety plan reflects the current evacuation capabilities of the residents.

(d) Fire drills. An assisted living facility must conduct at least one quarterly fire drill on each shift with at least one drill each month. Each drill must meet these requirements:

  (1) An assisted living facility must ensure staff take part in fire drills according to the assisted living facility's fire safety plan.

  (2) An assisted living facility must inform residents of evacuation procedures and locations of exits.

  (3) An assisted living facility must document every fire drill using the most current version of the required Texas Health and Human Services (HHSC) form titled "Fire Drill Report" available on the HHSC website.

  (4) A large Type B assisted living facility must activate the fire alarm signal during a fire drill conducted between 6:00 a.m. and 9:00 p.m.

  (5) An assisted living facility may announce a fire drill to residents in advance.

(e) Reporting fires.

  (1) An assisted living facility must immediately report a fire causing injury or death to a resident.

  (2) An assisted living facility must report a fire causing damage to the facility or facility equipment to HHSC within 72 hours after the fire is extinguished.

  (3) After making a report by telephone or email, an assisted living facility must file a written report using the most current version of the required HHSC form titled "Fire Report for Long Term Care Facilities" available on the HHSC website.

(f) Smoking policies. An assisted living facility must establish and enforce policies regarding smoking, even if the policy is that smoking will not be permitted. The policy must also address the use of e-cigarettes and vaping devices. If smoking will be permitted, the smoking policies must:

  (1) designate smoking areas for residents and staff; and

  (2) provide ashtrays of noncombustible material and safe design in smoking areas.

(g) Fire alarm system. An assisted living facility must establish a program to inspect, test, and maintain the fire alarm system according to the requirements of NFPA 72, and according to the requirements of NFPA 720 where carbon monoxide detection is provided, and must execute the program at least once every six months.

  (1) An assisted living facility must contract with a company that holds an Alarm Certificate of Registration from the State Fire Marshal's Office to execute the program.

  (2) An assisted living facility must ensure a company that performs a service under the contract required under paragraph (1) of this subsection completes, signs, and dates an inspection form like the inspection and testing form in NFPA 72 for a service provided under the contract.

  (3) If a task required by NFPA 72 or NFPA 720 must occur at intervals other than during the contracted visits in this subsection, an assisted living facility must ensure the task is performed and documented by a knowledgeable individual.

  (4) An assisted living facility must ensure:

    (A) a fire alarm system component that requires visual inspection is visually inspected in accordance with NFPA 72;

    (B) a fire alarm system component that requires testing is tested in accordance with NFPA 72; and

    (C) a fire alarm system component that requires maintenance is maintained in accordance with NFPA 72.

  (5) An assisted living facility that provides carbon monoxide detection must ensure:

    (A) a carbon monoxide detection component that requires visual inspection is visually inspected in accordance with NFPA 720;

    (B) a carbon monoxide detection component that requires testing is tested in accordance with NFPA 720;

    (C) a carbon monoxide detection component that requires maintenance is maintained in accordance with NFPA 720; and

    (D) a facility with a carbon monoxide detection component installed before August 31, 2021, must perform visual inspection, testing, and maintenance of that component beginning no later than August 31, 2022.

  (6) A large assisted living facility containing smoke compartments must ensure each required smoke damper is inspected and tested in accordance with NFPA 101.

  (7) An assisted living facility must ensure smoke detector sensitivity is checked within one year after installation and every two years thereafter in accordance with test methods in NFPA 72.

  (8) An assisted living facility must maintain onsite documentation of compliance with this subsection and must maintain record copies of documents regarding the installation of a fire alarm system, including as-built installation drawings, operation and maintenance manuals, the installation certificate for the system, and written sequences for its operation.

  (9) An assisted living facility must make documentation described in paragraph (8) of this subsection available to HHSC on request.

(h) Fire sprinkler system. An assisted living facility that is equipped with a fire sprinkler system, including a fire sprinkler system meeting NFPA 13D, must establish a program to inspect, test, and maintain the fire sprinkler system according to the requirements of NFPA 25, and must execute the program at least once every six months.

  (1) An assisted living facility must contract with a company that holds an appropriate Sprinkler Certificate of Registration from the State Fire Marshal's Office to execute the program.

  (2) An assisted living facility must ensure a company that performs a service under the contract required under paragraph (1) of this subsection completes, signs, and dates an inspection form like the inspection and testing form in NFPA 25 for a service provided under the contract.

  (3) If a task required by NFPA 25 must occur at intervals other than during the contracted visits in this subsection, an assisted living facility must ensure the task is performed and documented by knowledgeable individuals.

  (4) An assisted living facility must ensure that a sprinkler system component that requires visual inspection is visually inspected in accordance with NFPA 25.