<<Prev Rule

Texas Administrative Code

Next Rule>>
TITLE 16ECONOMIC REGULATION
PART 1RAILROAD COMMISSION OF TEXAS
CHAPTER 9LP-GAS SAFETY RULES
SUBCHAPTER BLP-GAS INSTALLATIONS, CONTAINERS, APPURTENANCES, AND EQUIPMENT REQUIREMENTS
RULE §9.131200 PSIG Working Pressure Stationary Vessels

In addition to NFPA 58, §5.2.4.2 and 5.9.2.5(A), 200 psig working pressure stationary vessels in LP-gas service in Texas prior to September 1, 1981, may be continued in service for commercial propane provided that they are fitted with pressure relief valves set for 250 psig normal start to discharge and comply with other provisions of this chapter. For the purpose of this section, "commercial propane" is defined as having a vapor pressure not in excess of 210 psig at 100 degrees Fahrenheit. This section does not apply to LP-gas motor fuel and mobile fuel containers.


Source Note: The provisions of this §9.131 adopted to be effective February 1, 2001, 26 TexReg 947; amended to be effective September 29, 2003, 28 TexReg 8318; amended to be effective February 1, 2008, 33 TexReg 122; amended to be effective January 6, 2020, 45 TexReg 127