(a) The following requirements apply in the Beaumont-Port
Arthur, Dallas-Fort Worth, and El Paso areas, as defined in §115.10
of this title (relating to Definitions). The control requirements
in this subsection no longer apply in the Dallas-Fort Worth area beginning
March 1, 2013.
(1) No person shall place, store, or hold in any storage
tank any volatile organic compounds (VOC) unless the storage tank
is capable of maintaining working pressure sufficient at all times
to prevent any vapor or gas loss to the atmosphere or is in compliance
with the control requirements specified in Table I(a) of this paragraph
for VOC other than crude oil and condensate or Table II(a) of this
paragraph for crude oil and condensate.
Attached Graphic
(2) For an external floating roof or internal floating
roof storage tank subject to the provisions of paragraph (1) of this
subsection, the following requirements apply.
(A) All openings in an internal floating roof or external
floating roof except for automatic bleeder vents (vacuum breaker vents)
and rim space vents must provide a projection below the liquid surface
or be equipped with a cover, seal, or lid. Any cover, seal, or lid
must be in a closed (i.e., no visible gap) position at all times except
when the device is in actual use.
(B) Automatic bleeder vents (vacuum breaker vents)
must be closed at all times except when the roof is being floated
off or landed on the roof leg supports.
(C) Rim vents, if provided, must be set to open only
when the roof is being floated off the roof leg supports or at the
manufacturer's recommended setting.
(D) Any roof drain that empties into the stored liquid
must be equipped with a slotted membrane fabric cover that covers
at least 90% of the area of the opening.
(E) There must be no visible holes, tears, or other
openings in any seal or seal fabric.
(F) For an external floating roof storage tank, secondary
seals must be the rim-mounted type (the seal must be continuous from
the floating roof to the tank wall). The accumulated area of gaps
that exceed 1/8 inch in width between the secondary seal and storage
tank wall may not be greater than 1.0 square inch per foot of tank
diameter.
(3) Vapor control systems, as defined in §115.10
of this title, used as a control device on any storage tank must maintain
a minimum control efficiency of 90%. If a flare is used, it must be
designed and operated in accordance with 40 Code of Federal Regulations §60.18(b)
- (f) (as amended through December 22, 2008 (73 FR 78209)) and be
lit at all times when VOC vapors are routed to the flare.
(b) The following requirements apply in Gregg, Nueces,
and Victoria Counties.
(1) No person shall place, store, or hold in any storage
tank any VOC, unless the storage tank is capable of maintaining working
pressure sufficient at all times to prevent any vapor or gas loss
to the atmosphere or is in compliance with the control requirements
specified in Table I(a) in subsection (a)(1) of this section for VOC
other than crude oil and condensate or Table II(a) in subsection (a)(1)
of this section for crude oil and condensate. If a flare is used as
a vapor recovery system, as defined in §115.10 of this title,
it must be designed and operated in accordance with 40 Code of Federal
Regulations §60.18(b) - (f) (as amended through December 22,
2008 (73 FR 78209)) and be lit at all times when VOC vapors are routed
to the flare.
(2) For an external floating roof or internal floating
roof storage tank subject to the provisions of paragraph (1) of this
subsection, the following requirements apply.
(A) All openings in an internal floating roof or external
floating roof, except for automatic bleeder vents (vacuum breaker
vents) and rim space vents, must provide a projection below the liquid
surface or be equipped with a cover, seal, or lid. Any cover, seal,
or lid must be in a closed (i.e., no visible gap) position at all
times, except when the device is in actual use.
(B) Automatic bleeder vents (vacuum breaker vents)
must be closed at all times except when the roof is being floated
off or landed on the roof leg supports.
(C) Rim vents, if provided, must be set to open only
when the roof is being floated off the roof leg supports or at the
manufacturer's recommended setting.
(D) Any roof drain that empties into the stored liquid
must be equipped with a slotted membrane fabric cover that covers
at least 90% of the area of the opening.
(E) There must be no visible holes, tears, or other
openings in any seal or seal fabric.
(F) For an external floating roof storage tank, secondary
seals must be the rim-mounted type (the seal shall be continuous from
the floating roof to the tank wall). The accumulated area of gaps
that exceed 1/8 inch in width between the secondary seal and tank
wall may not be greater than 1.0 square inch per foot of tank diameter.
(c) The following requirements apply in Aransas, Bexar,
Calhoun, Matagorda, San Patricio, and Travis Counties. The control
requirements of this subsection no longer apply for sources located
in Bexar County beginning January 1, 2025.
(1) No person may place, store, or hold in any storage
tank any VOC, other than crude oil or condensate, unless the storage
tank is capable of maintaining working pressure sufficient at all
times to prevent any vapor or gas loss to the atmosphere or is in
compliance with the control requirements specified in Table I(b) of
this paragraph for VOC other than crude oil and condensate.
Attached Graphic
(2) For an external floating roof or internal floating
roof storage tank subject to the provisions of paragraph (1) of this
subsection, the following requirements apply.
(A) There must be no visible holes, tears, or other
openings in any seal or seal fabric.
(B) All tank gauging and sampling devices must be vapor-tight
except when gauging and sampling is taking place.
(3) No person in Matagorda or San Patricio Counties
shall place, store, or hold crude oil or condensate in any storage
tank unless the storage tank is a pressure tank capable of maintaining
working pressures sufficient at all times to prevent vapor or gas
loss to the atmosphere or is equipped with one of the following control
devices, properly maintained and operated:
(A) an internal floating roof or external floating
roof, as defined in §115.10 of this title. These control devices
will not be allowed if the VOC has a true vapor pressure of 11.0 pounds
per square inch absolute (psia) or greater. All tank-gauging and tank-sampling
devices must be vapor-tight, except when gauging or sampling is taking
place; or
(B) a vapor control system as defined in §115.10
of this title.
(d) The following requirements apply in the Houston-Galveston-Brazoria
area, as defined in §115.10 of this title. The requirements in
this subsection no longer apply beginning March 1, 2013.
(1) No person shall place, store, or hold in any storage
tank any VOC unless the storage tank is capable of maintaining working
pressure sufficient at all times to prevent any vapor or gas loss
to the atmosphere or is in compliance with the control requirements
specified in either Table I(a) of subsection (a)(1) of this section
for VOC other than crude oil and condensate or Table II(a) of subsection
(a)(1) of this section for crude oil and condensate.
(2) For an external floating roof or internal floating
roof storage tank subject to the provisions of paragraph (1) of this
subsection, the following requirements apply.
(A) All openings in an internal floating roof or external
floating roof as defined in §115.10 of this title except for
automatic bleeder vents (vacuum breaker vents), and rim space vents
must provide a projection below the liquid surface. All openings in
an internal floating roof or external floating roof except for automatic
bleeder vents (vacuum breaker vents), rim space vents, leg sleeves,
and roof drains must be equipped with a deck cover. The deck cover
must be equipped with a gasket in good operating condition between
the cover and the deck. The deck cover must be closed (i.e., no gap
of more than 1/8 inch) at all times, except when the cover must be
open for access.
(B) Automatic bleeder vents (vacuum breaker vents)
and rim space vents must be equipped with a gasketed lid, pallet,
flapper, or other closure device and must be closed (i.e., no gap
of more than 1/8 inch) at all times except when required to be open
to relieve excess pressure or vacuum in accordance with the manufacturer's
design.
(C) Each opening into the internal floating roof for
a fixed roof support column may be equipped with a flexible fabric
sleeve seal instead of a deck cover.
Cont'd... |