<<Prev Rule

Texas Administrative Code

Next Rule>>
TITLE 26HEALTH AND HUMAN SERVICES
PART 1HEALTH AND HUMAN SERVICES COMMISSION
CHAPTER 510PRIVATE PSYCHIATRIC HOSPITALS AND CRISIS STABILIZATION UNITS
SUBCHAPTER GPHYSICAL PLANT AND CONSTRUCTION REQUIREMENTS
RULE §510.121Requirements for Buildings in which Existing Licensed Facilities are Located

(a) Compliance. All buildings in which existing facilities licensed by the department are located shall comply with this subsection.

  (1) Minimum fire safety and construction requirements.

    (A) Existing licensed facilities shall meet the requirements for health care occupancies contained in the 1985, 1988, 1991 or 2000 editions of the National Fire Protection Association 101, Code for Safety to Life from Fire in Buildings and Structures, (NFPA 101), and the facility licensing rules (1988, 1989 or 1994) under which the buildings or sections of buildings were constructed or last modified. All documents published by NFPA as referenced in this section may be obtained by writing or calling the NFPA at the following address or telephone number: National Fire Protection Association, 1 Batterymarch Park, P.O. Box 9101, Quincy, MA 02269-9101 or (800) 344-3555.

    (B) Existing facilities or portions of existing facilities constructed prior to the adoption of any of the editions of NFPA 101, the Facility Licensing Standards, and the facility licensing rules listed in subparagraph (A) of this paragraph, shall comply with this section and Chapter 19, NFPA 101, 2000 edition.

    (C) Compliance with the requirements of Chapter 3 of the National Fire Protection Association 101A, Alternative Approaches to Life Safety, 1998 edition, (relating to Fire Safety Evaluation System for Health Care Occupancies) will be acceptable in lieu of complying with the requirements of Chapter 19, NFPA 101, 2000 edition.

  (2) Remodeling of existing facilities. All requirements listed in this chapter relating to new construction are applicable to renovations, additions and alterations unless stated otherwise.

    (A) Alteration or installation of new equipment. Any alteration or any installation of new equipment shall be accomplished as nearly as practicable with the requirements for new construction, except that when existing conditions make changes impractical to accomplish, minor deviations from functional requirements may be permitted if the intent of the requirements is met and if the care and safety of patients will not be jeopardized. A request for deviation must be submitted in writing to the Hospital Licensing Director, Health Facility Licensing and Compliance Division, Texas Department of Health, 1100 West 49th Street, Austin, Texas 78756, and approved by the department.

    (B) Installation, alteration, or extension approval. No new system of mechanical, electrical, plumbing, fire protection, or piped medical gas system may be installed or any such existing system be replaced, materially altered or extended in an existing building licensed as a facility, until complete plans and specifications for the replacement, installation, alteration, or extension have been submitted to the department, reviewed and approved in accordance with §134.127 of this title (relating to Preparation, Submittal, Review and Approval of Plans).

    (C) Minor remodeling or alterations. All remodeling or alterations which do not involve alterations to load bearing members or partitions, change functional operation, affect fire safety (e.g. modifications to the fire, smoke, and corridor walls), add or subtract beds or services for which the facility is licensed, and do not involve changes listed in subparagraph (B) of this paragraph, shall be submitted for approval without submitting contract documents. Such approval shall be requested in writing with a brief description of the proposed changes and a simple floor plan for evaluation and determination of disposition.

    (D) Major remodeling or alterations. Plans shall be submitted in accordance with §134.127 of this title for all major remodeling or alterations. All remodeling or alterations which involve alterations to load bearing members or partitions, change functional operation, affect fire safety (e.g. modifications to the fire, smoke, and corridor walls), or change the designed bed capacity or services over those for which the facility is licensed are considered as major remodeling and alterations.

    (E) Phasing of construction in existing facilities. Projects involving alterations of and additions to existing buildings shall be programmed and phased so that on-site construction will minimize disruptions of existing functions. Access, exit access, and fire protection shall be maintained so that the safety of the occupants will not be jeopardized during construction. Dust and vapor barriers shall be provided to separate areas undergoing demolition and construction from occupied areas. Temporary sound barriers shall be provided where intense prolonged construction noises will disturb patients or staff in the occupied portions of the building.

    (F) Nonconforming conditions. When doing renovation work, if it is found to be infeasible to correct all of the nonconforming conditions in the existing facility in accordance with these rules, a conditional approval may be granted by the department if the operation of the facility, necessary access by the handicapped, and safety of the patients are not jeopardized by the nonconforming condition.

(b) Previously licensed facilities. Buildings which have been licensed previously as facilities but have been vacated or used for purposes other than as facilities and which are not in compliance with the 1985, 1988, 1991 or 2000 editions of the NFPA 101, and facility licensing rules (1988, 1989 or 1994) under which the building or sections of buildings were constructed shall comply with the requirements of §134.122 of this title (relating to New Construction Requirements), §134.123 of this title (relating to Spatial Requirements for New Construction), §134.125 of this title (relating to Building with Multiple Occupancies), §134.127 of this title, and §134.130 of this title (relating to Record Drawings, Manuals and Design Data), inclusively.


Source Note: The provisions of this §510.121 adopted to be effective January 1, 2004, 28 TexReg 5154; transferred effective June 1, 2019, as published in the Texas Register May 17, 2019, 44 TexReg 2469

Link to Texas Secretary of State Home Page | link to Texas Register home page | link to Texas Administrative Code home page | link to Open Meetings home page